The formula, in one line

Runtime has no hidden variables:

  • Runtime (hours) = tank size (gallons) ÷ fuel per hour (gal/h)
  • Fuel per hour = kW drawn × SFC (0.16 gal/kW/h for gasoline)

Put the 5 kW example through it: 3.75 kW × 0.16 = 0.60 gal/h, then 5 ÷ 0.60 = 8.33 hours — 8 h 20 min. Two steps, and you can check any claim on any brochure in under a minute.

Runtime by tank size

The same 5 kW gasoline generator at 75% load (0.60 gal/h), across the tank sizes portable machines actually ship with:

Tank size Litres Runtime at 75% load Refuel stops per 24 h
1 gallon3.8 L1 h 40 min14
2 gallons7.6 L3 h 20 min7
5 gallons18.9 L8 h 20 min2
10 gallons37.9 L16 h 40 min1
20 gallons75.7 L33 h 20 min0

Two rows in that table are not like the others. At 1 gallon the machine runs 1 hour 40 minutes — under two hours — which is where most portable inverter generators land. That is the number that decides whether you sleep through a storm or get up to refuel.

The 2-hour rule

Any generator whose full-tank runtime falls below about 2 hours is, practically speaking, a daytime tool. Under that threshold you are refuelling 12 or more times a day, in the dark, next to a hot exhaust, with a jerry can. It is not a safety lecture so much as an arithmetic one: nobody keeps that up for a full night.

Use it as a buying filter: if the calculated runtime on a full tank is under 2 hours, the tank is too small for unattended use. Fix it with a bigger tank, an external fuel line, a larger generator run at lower load — or by simply accepting that you will be awake with it.

Runtime by load: the lever that actually matters

Same 5 kW generator, same 5-gallon tank, four load settings:

Load Power drawn Fuel per hour Runtime on 5 gal
25%1.25 kW0.20 gal25 h 0 min
50%2.50 kW0.40 gal12 h 30 min
75%3.75 kW0.60 gal8 h 20 min
100%5.00 kW0.80 gal6 h 15 min

Runtime is inversely proportional to load — cut the load in half, double the time. Which is why the cheapest upgrade for longer runtime is not a bigger tank, it is unplugging the water heater and letting the fridge cycle on its own. A fridge averages a few hundred watts; running it on a 5 kW generator puts you near the bottom of that table, at 20-plus hours on one fill.

Runtime by generator size

If you are choosing between sizes, here is how long a 5-gallon tank lasts at 75% load for the common portable range (0.12 gal/kW/h effective burn rate):

Generator size Fuel per hour Runtime on 5 gal
2000 W0.24 gal20 h 50 min
3500 W0.42 gal11 h 54 min
5000 W0.60 gal8 h 20 min
7500 W0.90 gal5 h 33 min
10000 W1.20 gal4 h 10 min

Bigger engines are not thirstier for the sake of it — they are supplying more power, and fuel use tracks power output almost exactly. The efficiency win comes from not buying more generator than you need.

Five ways to stretch a tank

  • Run eco-mode. Most inverter generators drop to 50% or less of rated load for steady work, roughly doubling runtime.
  • Shed the phantom loads. Water heaters, AC units and electric kettles are what push you from the 50% row to the 100% row. If you are not sure which appliances deserve to stay on, the ranked appliance cost table shows what each one draws in normal use.
  • Keep the air filter clean. A clogged filter richens the mixture and costs fuel, power and engine life at the same time.
  • Do not let the tank run dry. Beyond the obvious stop, an empty tank sucks debris into the carburettor — the single most common way portable generators die.
  • Store fuel properly. Fresh gasoline, or fuel stabiliser if the machine will sit. Old fuel causes hard starts that make people think the generator failed.

try it with your tank

Generator Fuel Runtime & Cost Estimator

Enter your generator size, fuel type, tank size and load. You get fuel per hour, full-tank runtime, cost to fill and cost per hour — and a red warning when runtime drops under 2 hours.

Open the calculator

faq

Frequently Asked Questions

Tank sizing, overnight runtime and the tweaks that buy you extra hours.

How long will a generator run on a full tank?

Divide the tank size by fuel consumed per hour. A 5 kW gasoline generator at 75% load burns 0.60 gallons per hour, so a 5-gallon tank lasts about 8 hours 20 minutes. The same tank lasts 6 hours 15 minutes at full load and 12 hours 30 minutes at 50% load.

What size fuel tank do I need for overnight power?

For an unattended 8-hour night on a 5 kW gasoline generator, plan on at least 5 gallons (19 litres) — the point where runtime reaches about 8 hours at 75% load. Below 2 gallons the machine needs refuelling every 1 to 3 hours, which makes it impractical for overnight use.

How do I make my generator run longer on a tank?

Drop the load: cutting from 100% to 50% roughly doubles runtime, from 6.25 to 12.5 hours on a 5-gallon tank. Remove unloaded appliances, use eco-mode, keep the air filter clean, and never let the tank sit below a quarter — stale, empty tanks cause the carburettor problems that end generator lives.